Notes for each tank style
Single Wall Vertical
A flat-bottom upright tank that sits directly on its base.
- Support the whole flat bottom: no gaps, rocks or debris under the tank.
- Use flexible connections on fittings low on the sidewall, where the wall moves most as the tank fills and empties.
- Listed capacity is calculated to the top of the straight sidewall. The tank may be filled "brim" full if it is done with care.
Double Wall Vertical
A tank within a tank: the outer tank holds the contents if the inner tank ever leaks.
- The inner and outer tanks are joined at our plant by thermoplastic welding, so the tank ships and installs as one unit.
- Lift only by the OUTER tank's lifting lugs. The inner tank's lugs are normally plugged.
- The leak detector ships separately (so does an ultrasonic level sensor, if ordered). The leak detector needs no setup or calibration: test it by dipping the sensor in water, then install it in the secondary (interstitial) space between the walls.
- A sight glass is never used on a double wall tank. A reverse float level indicator works well because it needs no sidewall penetrations.
Insulated Single Wall
Foam insulation and an outer jacket keep the contents at temperature.
- Never drill into or mount anything on an insulated tank.
- A temperature controller is always included and comes mounted on the tank, factory pre-wired and tested. On site, only connect the incoming 120 VAC single-phase supply to the designated terminal blocks. Don't change any other wiring.
- Heat comes from HTD SPX adhesive-backed heater pads (210 or 420 watts, 120 VAC; 240 VAC options are available). The HTD controller has a process thermostat and an over-temperature cut-out, each adjustable from 50 to 175°F, in a NEMA 4X enclosure, and is approved for unclassified (non-hazardous) locations; a hazardous-area version is available. Wiring practice follows the NEC (NFPA 70) and IEEE 515.
- Insulation adds to the outside size: 2" insulation makes the tank about 4" wider and 2" taller, 3" about 6" wider and 3" taller, and 4" about 8" wider and 4" taller.
Insulated Double Wall
Containment and temperature control in one unit.
- Follow both the Double Wall and the Insulated Single Wall instructions on this page.
- Lift only by the outer tank's lifting lugs, and never drill into or mount anything on the insulated jacket.
- Insulation adds to the outside size: 2" insulation makes the tank about 4" wider and 2" taller, 3" about 6" wider and 3" taller, and 4" about 8" wider and 4" taller.
Cone Bottom
A sloped bottom drains completely. The tank sits in a stand, never on its cone.
- The stand is optional and sold separately.
- If you supply your own stand, it must support the full weight of the tank and its contents, including the liquid in the cone. Stands are commonly made of steel, aluminum or molded plastic.
- Set the stand on a level, solid base. The cone must not touch the ground or the pad.
- Support the bottom outlet valve and its piping separately so their weight doesn't hang on the outlet, and leave room under the cone to reach the valve.
Open Top Cone Bottom
Open for mixing and processing; installed the same way as a cone bottom tank.
- Follow the Cone Bottom instructions: the stand is optional and sold separately, and any stand must support the full weight of the tank and its contents.
- Don't rest equipment on the open rim of the tank.
Horizontal
Horizontal leg tanks and elliptical leg tanks for low clearance and for hauling.
- Every leg must rest on a flat, horizontal surface.
- Horizontal leg tanks and elliptical leg tanks are commonly mounted on trucks and trailers for water hauling and spraying. Nearly all sizes can be, as long as the truck or trailer is matched to the tank.
- Every horizontal tank comes with bands or straps for mounting it to the vehicle.
Rectangular
Space-saving tanks for tight rooms and process lines.
- No frame is needed.
- Support the full flat bottom on a level surface.
- Support piping separately; keep its weight off the tank walls.
Keep it in good shape
Inspect the tank at least weekly for leaks around the fittings, check the tie-downs and vents monthly, and give it a full inspection once a year. See Sanitation Info for cleaning and Measurement Info for sizing, strapping charts and level gauges.